| VD26 Series | This is a SINGLE DISPLAY on/off or proportional DIN controller range for use in SIMPLE APPLICATIONS WHERE THREE TERM CONTROL IS NOT REQUIRED |
| VT26 Series | "FUZZY LOGIC" enhanced Dual Display "Auto-tuning" PID (Three term) DIN controller range for use WHERE ACCURACY IS IMPORTANT |
| VT30 Series | "FUZZY LOGIC" enhanced Dual Display "Auto-tuning" PID (Three term) DIN controller range INCORPORATING PATTERN PROFILE CONTROL IN 16 STEPS RAMP AND SOAK c/w a host of features and event alarms |
TECHNICAL COMPARRISON
VD26 Series |
VT26 Series |
VT30 Series |
|||||
| Size | 48w x 48h x 100d | VD2600 |
VT4826 |
VT4830 |
|||
| 96w x 96h x 80d | VD2604 |
VT9626 |
VT9630 |
||||
| 72w x 72h x 80d | VD2601 |
VT7226 |
VT7230 |
||||
| 96w x 48h x 80d | VD2603 |
VT9426 |
|||||
| 48w x 96h x 80d | VT4926 |
VT4930 |
|||||
VD26 Series |
VT26 Series |
VT30 Series |
|||||
| Inputs | Thermocouple |
J |
• |
• |
• |
||
K |
• |
• |
• |
||||
B |
• |
• |
• |
||||
R |
• |
• |
• |
||||
S |
• |
• |
• |
||||
T |
• |
• |
• |
||||
E |
• |
• |
• |
||||
N |
• |
• |
• |
||||
C |
• |
• |
• |
||||
| RTD's | PT100 din |
• |
• |
• |
|||
PT100 jis |
• |
• |
• |
||||
| Linear | • |
• |
• |
||||
VD Series |
VT20 Series |
VT30 Series |
|||||
| Remote Set Point (Option) | None |
DC Linear |
None |
||||
| Output 1 | Relay | • |
• |
• |
|||
| Solid State Relay | • |
• |
• |
||||
| Linear Current (0/4~20 mA) | • |
• |
• |
||||
| Linear Voltage (0/1~5Vdc) | • |
• |
• |
||||
Output 2 As optional Extra |
Relay | • |
• |
• |
|||
| Solid State Relay | • |
• |
• |
||||
| Linear Current (0/4~20 mA) | • |
• |
• |
||||
| Linear Voltage (0/1~5Vdc) | • |
• |
• |
||||
VD Series |
VT20 Series |
VT30 Series |
|||||
| Alarms | 1 x Std |
2 x Standard on all models | 2 x Standard on all models | ||||
| Control Action | ON/OFF |
• |
• |
• |
|||
P |
• |
• |
• |
||||
PD |
• |
• |
• |
||||
Auto-Tune
PID |
• |
• |
|||||
Auto-Tune
Fuzzy Enhanced PID |
• |
• |
|||||
VD26 Series |
VT26 Series |
VT30 Series |
|||||
| Special Ramp Features | One step ramp + soak (Soft Start) | ||||||
| Pattern Programmable 2 x 8-segment ramp & soak profiles or 16 segment continuous c/w event alarms etc |
• |
||||||
| Retransmission Facilities | Optional extra | PV only DC Linear | PV or SV DC Linear | PV or SV DC Linear | |||
| Modbus RS485 | Optional extra | • |
• |
• |
|||
VD26 Series |
VT26 Series |
VT30 Series |
|||||
| Accuracy | Thermocouple | ± 1 °C |
± 1 °C |
± 1 °C |
|||
| PT100 (RTD) | ± 0.2 °C |
± 0.2 °C |
± 0.2 °C |
||||
| Linear (4~20 etc) | ± 3 µV |
± 3 µV |
± 3 µV |
||||
| Power (Mains) | All models come standard with
90~264 Vac 50/60hz or 90~264 Vdc 18~32 V AC or DC is available as an option |
||||||
| 24 Vdc Auxiliary Power for use in powering 4~20 mA 4 wire transducers | Available on all VD26, VT26 and VT30 models except the 48 x 48 size units. | ||||||