Programmable Head Mount Thermocouple or PT100 Transmitter Easy to use Easy and Calibrate ! |
The
iSignalTrans IST-H "Head Mount" transmitter can be configuration using
a PC with iSignalTrans software and interface cable. "iSignalWin"
is our user-friendly calibration software. The latest release version can be
download free from our website. The transmitter can be calibrated in the workshop
without connection to any wiring or power source.

| Input | Thermocouple (T/C) : industry standard thermocouple types J, K, T, E, B, R, S, N, C (ITS-90). |
| Pt100: Excitation 180uA. 2 or 3 wire connection (ITS-90 a =0.00385). | |
| Voltage: -60 mV dc to 60 mV dc or -10Vdc to 10V dc. | |
| Current : 0-24 mA dc (optional ) | |
| Accuracy | Refer to Table 1.Input Signal |
| A/D Resolution | 16 bits |
| Input Sampling Rate | <200 ms |
| Power supply | DC 10 to 36 V, |
| Max Load | (V-10)/0.02 ohm |
| Humidity | 0 to 90% RH |
| Output Resolution | 0.6 µA (15 bits) |
| Output Responce Time | <200 ms |
| Common Mode Rejection Ratio (CMRR) | >80 dB |
| Electromagnetic compatibility | En 50081-2, En 50082-2 |
| Galvanic isolation | 4 KV between input and output |
| Operating temperature | -40 to 85 ºC |
| Humidity | 0~90% RH |
|
2
YEAR WARRANTY
![]()
back
to top
Back
to Main Page
QIS is the UK sole importer and European outlet
for the VERTEX product
We provide full sales , technical and after sales service for this product