Programmable DIN Rail Thermocouple & PT100 Transmitter

Easy to use Easy and Calibrate !

The iSignalTrans IST-D "DIN rail" transmitter can be configuration using a PC with iSignalTrans software and interface cable. "iSignalWin" is our user-friendly calibration software. The latest release version can be download free from our website. The transmitter can be calibrated in the workshop without connection to any wiring or power source.


Specification:
     

 

Input Thermocouple (T/C) : industry standard thermocouple types J, K, T, E, B, R, S, N, C (ITS-90).
Pt100: Excitation 180uA. 2 or 3 wire connection (ITS-90 a =0.00385).
Voltage: -60 mV dc to 60 mV dc or -10Vdc to 10V dc.
Current : 0-24 mA dc
A/D Resolution 16 bits
Power supply DC 12 to 35 V,
Accuracy Refer to Table 1.Input Signal
Humidity 0 to 90% RH
Output Resolution 0.6 µA (15 bits)
Operating temperature -40 to 85 ºC
Electromagnetic compatibility En 50081-2, En 50082-2
Galvanic isolation 4 KV 1min. between input and output
Dimension 75mm (W)x 87mm (H)x 18.5mm (D)
Response time <200ms
  1. Calibration is done using a USB port on your PC and a special USB cable that includes an interface adaption. This cable is avaliable from us and it's code is URC-1020.
  2. Selection of different thermocouples or PT100 inputs and configuration of ranges is via the software.
  3. Selection of mV, V or mA inputs involves on-board dip switch selection.
  4. We are in the process of developing a hand held programmer to facilitate simple configuration and input selection.
Input signal Maximum Range Accuracy
Thermocouple J -50 to 1000 ºC (-58 to 1832 ºF ) ± 1 ºC
Thermocouple K -50 to 1370 ºC (-58 to 2498 ºF ) ± 1 ºC
Thermocouple T -270 to 400 ºC (-454 to 752 ºF ) ± 1 ºC
Thermocouple E -50 to 960 ºC (-58 to 1760 ºF ) ± 1 ºC
Thermocouple B 0 to 1750 ºC (32 to 3182 ºF ) ± 2 ºC (Note1)
Thermocouple R -50 to 1750 ºC (-58 to 3182 ºF ) ± 2 ºC
Thermocouple S -50 to 1750 ºC (-58 to 3182 ºF ) ± 2 ºC
Thermocouple N -50 to 1300 ºC (-58 to 2372 ºF ) ± 2 ºC
Thermocouple C -50 to 1800 ºC (-58 to 3272 ºF ) ± 2 ºC
Pt100 -200 to 600 ºC (-328 to 1112 ºF ) ± 0.2 ºC
mV -60mVto 60mV ± 0.01m V
Voltage (Note2) -10 to 10Vdc ± 1m V
Current (Note2) 0 to 24mAdc ± 10µA
Table 1.Input Signal
Note 1 : Accuracy is not guaranteed between 0 and 400 ºC (0 and 752 ºF) for type B, R and S.
Note 2 : The internal dip switches are used for these inputs.
 
Layout and connections
 
 
 
Dimensions:
 
 
 
Ordering Information:
 
       

2 YEAR WARRANTY


back to top
Back to Main Page


QIS is the UK sole importer and European outlet for the VERTEX product

We provide full sales , technical and after sales service for this product

Contact us we are here to advise and help